Cyber-Resilient System Identification for Power Grid through Bayesian Integration
2510.14043v1
eess.SY, cs.AI, cs.CR, cs.SY
2025-10-18
Авторы:
Shimiao Li, Guannan Qu, Bryan Hooi, Vyas Sekar, Soummya Kar, Larry Pileggi
Abstract
Power grids increasingly need real-time situational awareness under the
ever-evolving cyberthreat landscape. Advances in snapshot-based system
identification approaches have enabled accurately estimating states and
topology from a snapshot of measurement data, under random bad data and
topology errors. However, modern interactive, targeted false data can stay
undetectable to these methods, and significantly compromise estimation
accuracy. This work advances system identification that combines snapshot-based
method with time-series model via Bayesian Integration, to advance cyber
resiliency against both random and targeted false data. Using a distance-based
time-series model, this work can leverage historical data of different
distributions induced by changes in grid topology and other settings. The
normal system behavior captured from historical data is integrated into system
identification through a Bayesian treatment, to make solutions robust to
targeted false data. We experiment on mixed random anomalies (bad data,
topology error) and targeted false data injection attack (FDIA) to demonstrate
our method's 1) cyber resilience: achieving over 70% reduction in estimation
error under FDIA; 2) anomalous data identification: being able to alarm and
locate anomalous data; 3) almost linear scalability: achieving comparable speed
with the snapshot-based baseline, both taking <1min per time tick on the large
2,383-bus system using a laptop CPU.